What is best way to wire a ceiling receptacle in this situation? Planned maintenance scheduled April 23, 2019 at 23:30 UTC (7:30pm US/Eastern) Announcing the arrival of Valued Associate #679: Cesar Manara Unicorn Meta Zoo #1: Why another podcast?How do I wire a switch/receptacle combination?Is there some kind of adapter for an old ceiling box?Rewiring a switch controlled receptacle to a ceiling lightOddball wiring for ceiling lightWhat is the purpose of these removable “collars” on ceramic light fixturesHow close can light be to exposed insulation?Convert light fixture to receptacleWill cutting section of 2x4 reduce strengthWiring a ceiling light to a switched receptacleRunning wire in basement with drop ceiling

Intuitive explanation of the rank-nullity theorem

How would a mousetrap for use in space work?

Drawing spherical mirrors

How to save space when writing equations with cases?

If Windows 7 doesn't support WSL, then what is "Subsystem for UNIX-based Applications"?

How does Belgium enforce obligatory attendance in elections?

What to do with repeated rejections for phd position

How were pictures turned from film to a big picture in a picture frame before digital scanning?

Can the Flaming Sphere spell be rammed into multiple Tiny creatures that are in the same 5-foot square?

Amount of permutations on an NxNxN Rubik's Cube

Why do early math courses focus on the cross sections of a cone and not on other 3D objects?

Co-worker has annoying ringtone

What is best way to wire a ceiling receptacle in this situation?

How do I find out the mythology and history of my Fortress?

Did Mueller's report provide an evidentiary basis for the claim of Russian govt election interference via social media?

What is the meaning of 'breadth' in breadth first search?

Most bit efficient text communication method?

Can a sorcerer use careful spell on himself?

1-probability to calculate two events in a row

AppleTVs create a chatty alternate WiFi network

An adverb for when you're not exaggerating

What is the difference between a "ranged attack" and a "ranged weapon attack"?

How to compare two different files line by line in unix?

Putting class ranking in CV, but against dept guidelines



What is best way to wire a ceiling receptacle in this situation?



Planned maintenance scheduled April 23, 2019 at 23:30 UTC (7:30pm US/Eastern)
Announcing the arrival of Valued Associate #679: Cesar Manara
Unicorn Meta Zoo #1: Why another podcast?How do I wire a switch/receptacle combination?Is there some kind of adapter for an old ceiling box?Rewiring a switch controlled receptacle to a ceiling lightOddball wiring for ceiling lightWhat is the purpose of these removable “collars” on ceramic light fixturesHow close can light be to exposed insulation?Convert light fixture to receptacleWill cutting section of 2x4 reduce strengthWiring a ceiling light to a switched receptacleRunning wire in basement with drop ceiling



.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;








1















I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here










share|improve this question






























    1















    I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here










    share|improve this question


























      1












      1








      1








      I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here










      share|improve this question
















      I was trying to rewire this garage door opener where in current situation it is not code compliant to where it is. The picture above shows where a porcelain light socket was wired. I had hoped to use it for receptacle but the cover is too big for the box and the one that does fit is too recessed in ceiling. Behind the middle of box in picture is cross piece that is mounted between two ceiling joists. I had thought of keeping light and make another hole in ceiling for receptacle box. How close could the porcelain light fixture and receptacle be to each other to be code compliant? Using Led bulb in socket and both are on same circuit.enter image description here







      electrical wiring receptacle






      share|improve this question















      share|improve this question













      share|improve this question




      share|improve this question








      edited 1 hour ago









      Machavity

      8,46821942




      8,46821942










      asked 2 hours ago









      georgia-guygeorgia-guy

      1149




      1149




















          2 Answers
          2






          active

          oldest

          votes


















          2














          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer























          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago


















          0














          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer























          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            40 mins ago











          Your Answer








          StackExchange.ready(function()
          var channelOptions =
          tags: "".split(" "),
          id: "73"
          ;
          initTagRenderer("".split(" "), "".split(" "), channelOptions);

          StackExchange.using("externalEditor", function()
          // Have to fire editor after snippets, if snippets enabled
          if (StackExchange.settings.snippets.snippetsEnabled)
          StackExchange.using("snippets", function()
          createEditor();
          );

          else
          createEditor();

          );

          function createEditor()
          StackExchange.prepareEditor(
          heartbeatType: 'answer',
          autoActivateHeartbeat: false,
          convertImagesToLinks: false,
          noModals: true,
          showLowRepImageUploadWarning: true,
          reputationToPostImages: null,
          bindNavPrevention: true,
          postfix: "",
          imageUploader:
          brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
          contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
          allowUrls: true
          ,
          noCode: true, onDemand: true,
          discardSelector: ".discard-answer"
          ,immediatelyShowMarkdownHelp:true
          );



          );













          draft saved

          draft discarded


















          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162387%2fwhat-is-best-way-to-wire-a-ceiling-receptacle-in-this-situation%23new-answer', 'question_page');

          );

          Post as a guest















          Required, but never shown

























          2 Answers
          2






          active

          oldest

          votes








          2 Answers
          2






          active

          oldest

          votes









          active

          oldest

          votes






          active

          oldest

          votes









          2














          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer























          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago















          2














          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer























          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago













          2












          2








          2







          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here






          share|improve this answer













          They make lampholders that have an outlet built in. Solves the problem of mounting this to that octagon box.



          enter image description here







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 1 hour ago









          MachavityMachavity

          8,46821942




          8,46821942












          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago

















          • I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

            – georgia-guy
            1 hour ago











          • Unless you think that light circuit is overloaded, this should be good enough to run a door opener

            – Machavity
            1 hour ago
















          I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

          – georgia-guy
          1 hour ago





          I had thought of that, but I was always concerned about how good the receptacle coming off the light socket would be. The garage door opener would be the only thing plugged into it (1/2 hp chain drive garage door opener).

          – georgia-guy
          1 hour ago













          Unless you think that light circuit is overloaded, this should be good enough to run a door opener

          – Machavity
          1 hour ago





          Unless you think that light circuit is overloaded, this should be good enough to run a door opener

          – Machavity
          1 hour ago













          0














          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer























          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            40 mins ago















          0














          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer























          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            40 mins ago













          0












          0








          0







          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.






          share|improve this answer













          I like Machavity's solution. The only problem would be that the box and wire are probably switched at the wall since there is a keyless socket there now. That would mean your opener would be on that switch. There would be nothing wrong with that unless somebody turns the switch off and then your opener would not work. That could work as a security type of 'vacation mode' where you could turn off your opener when you are away. I put a controlled plug-in adapter with a wireless remote for my mother-in-law because she had her door opened by somebody driving by. She turns it off at night or if she is not expecting us to come over.



          I can't tell you code wise on the distance, but make sure if you put in another box it is 'ceiling rated'. A lot of cut-in old work boxes are only wall rated and this would affect the fire rating of your ceiling. I wouldn't suggest putting that wire in the same octagon box in the picture because you could end up with 240 volts in that box depending on which leg the wires come off your panel. Lastly, don't use a residential grade receptacle, pay the couple of dollars more for a commercial receptacle because these will grip the plug blades better.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 48 mins ago









          lqlarrylqlarry

          7,18711336




          7,18711336












          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            40 mins ago

















          • It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

            – georgia-guy
            40 mins ago
















          It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

          – georgia-guy
          40 mins ago





          It is switched at the wall in kitchen nearby. Before it was run from switch in kitchen to junction box in attic and from there to door opener and light socket. I would be eliminating one of the runs of wire by using socket and receptacle together like above. Is the box you are talking about can be found at the big box home improvement stores? I didn't remember seeing that type there.

          – georgia-guy
          40 mins ago

















          draft saved

          draft discarded
















































          Thanks for contributing an answer to Home Improvement Stack Exchange!


          • Please be sure to answer the question. Provide details and share your research!

          But avoid


          • Asking for help, clarification, or responding to other answers.

          • Making statements based on opinion; back them up with references or personal experience.

          To learn more, see our tips on writing great answers.




          draft saved


          draft discarded














          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162387%2fwhat-is-best-way-to-wire-a-ceiling-receptacle-in-this-situation%23new-answer', 'question_page');

          );

          Post as a guest















          Required, but never shown





















































          Required, but never shown














          Required, but never shown












          Required, but never shown







          Required, but never shown

































          Required, but never shown














          Required, but never shown












          Required, but never shown







          Required, but never shown







          Popular posts from this blog

          Möglingen Índice Localización Historia Demografía Referencias Enlaces externos Menú de navegación48°53′18″N 9°07′45″E / 48.888333333333, 9.129166666666748°53′18″N 9°07′45″E / 48.888333333333, 9.1291666666667Sitio web oficial Mapa de Möglingen«Gemeinden in Deutschland nach Fläche, Bevölkerung und Postleitzahl am 30.09.2016»Möglingen

          Virtualbox - Configuration error: Querying “UUID” failed (VERR_CFGM_VALUE_NOT_FOUND)“VERR_SUPLIB_WORLD_WRITABLE” error when trying to installing OS in virtualboxVirtual Box Kernel errorFailed to open a seesion for the virtual machineFailed to open a session for the virtual machineUbuntu 14.04 LTS Virtualbox errorcan't use VM VirtualBoxusing virtualboxI can't run Linux-64 Bit on VirtualBoxUnable to insert the virtual optical disk (VBoxguestaddition) in virtual machine for ubuntu server in win 10VirtuaBox in Ubuntu 18.04 Issues with Win10.ISO Installation

          Antonio De Lisio Carrera Referencias Menú de navegación«Caracas: evolución relacional multipleja»«Cuando los gobiernos subestiman a las localidades: L a Iniciativa para la Integración de la Infraestructura Regional Suramericana (IIRSA) en la frontera Colombo-Venezolana»«Maestría en Planificación Integral del Ambiente»«La Metrópoli Caraqueña: Expansión Simplificadora o Articulación Diversificante»«La Metrópoli Caraqueña: Expansión Simplificadora o Articulación Diversificante»«Conózcanos»«Caracas: evolución relacional multipleja»«La Metrópoli Caraqueña: Expansión Simplificadora o Articulación Diversificante»